电池
电池容量 |
9 Ah |
电池充电时间 |
5 h |
电池电压 |
12 V |
全载典型备用时间 |
5 min |
冷启动 |
Y |
性能
噪音水平 |
50 dB |
波形 |
Sine |
UPS 拓扑 |
Double-conversion (Online) |
能量控制
输入工作电压(最大值) |
276 V |
输入工作电压(最小值) |
110 V |
效率 |
96% |
THD输出电压 |
5% |
电源输入频率 |
45/66 Hz |
THD输入电流 |
5% |
输出功率(瓦特-安培) |
10000 VA |
波峰因数 |
3:1 |
输出工作电压(最小值) |
208 V |
输出工作电压(最大值) |
240 V |
输入功率因数 |
0.99 |
输出功率因数 |
0.9 |
输出电压调节 |
1% |
输出功率 |
9000 W |
10000 VA, RS-232, USB, 100 ms, 110-276 VAC, 92 kg, Black
On-line Double Conversion
The B500 range was developed around the highest level of protection (On-line Double Conversion), this means that the output is VFI (Voltage& Frequency Independent) allowing the critical load power to be constantly maintained by the UPS inverter, this in turn means the load does not see any mains borne interferences and delivers a zero-break transition from utility power to battery.
More Power / Smaller Footprint
Ideal for all critical IT Environments where space is at a premium. The tower based UPS delivers up to 25% more usable power than other manufacturers thanks to a 0.9 Output Power Factor. The B500 also comes complete with internal batteries as standard, throughout the range, eliminating the need for external battery cabinets on standard run times, minimising the footprint and therefore maximising floor space for other equipment.
Highest Protection
The B500 includes a static and internal manual bypass switch as standard, with zero transfer time between inverter and bypass. The wide input voltage window reduces the amount of time spent on switching to or running on battery power, thereby increasing battery service life, UPS efficiency and reliability. A powerful internal charger enables backup times of up to 8 hours with a 6 hour recover time.
Frequency Converter
All of the B500 range can be used as a frequency converter.
Future Expansion or Redundancy
To future proof the investment in a B500 UPS, up to four additional units can be connected in parallel. The B500 is genuinely "easy parallel", all equipment needed for parallel operation is included within the initial purchase of the first unit making it very simple to provide further capacity or redundancy.
UPS Management
The B500 features an Intelligent Slot for the installation of programmable relay alarm cards, SNMP communication or RS485 MODBUS connection. In addition, the B500 has USB and RS232 communication for connection to a local server, a programmable dry relay contact, an EPO connection facility and a connection for interlocking with an external bypass switch as standard. The product comes complete with a free download of user friendly monitoring and shut-down software suitable for the majority of operating systems.
Generator Friendly
The rectifier stage of the B500 has been designed to provide a unity input power factor and Input Total Harmonic Distortion (THDi) of 5% maximum. This makes the UPS extremely generator friendly, increases efficiency and negates the need to oversize input cables and switchgear.