产品特点
| Shock resistant |
Y |
| 隔离度 |
0.5 kV |
| Wire clamp type |
Cage clamp |
| Line length |
1200 m |
| Baud rate |
115200 Bd |
| Strip length (max) |
9 mm |
| Vibration resistant |
Y |
能量控制
| 电流消耗 |
350 mA |
| Current consumption (internal) |
1650 mA |
Fieldbus Coupler MODBUS, RS-485, 115.2 kBd, DC 24 V
<b>Fieldbus Coupler MODBUS; RS-485; 115,2 kBd </b>
This fieldbus coupler allows connection of the WAGO‐I/O‐SYSTEM as a slave to the MODBUS or fieldbus.
The bus coupler recognizes all connected I/O modules and creates a local process image on this basis. Analog and specialty module data is sent via words and/or bytes; digital data is sent bit by bit.
The data of the analog modules is stored in the process image which is created automatically according to the order in which the modules are connected to the buscoupler. The bits of the digital modules are sent byte by byte and added to the analog data. If the amount of digital information exceeds 8 bits, the buscoupler automatically starts with a new byte.