Other features
| Conversion time |
500 ms |
| Signal direction |
Input |
Features
| Channels quantity |
2 |
| Isolation |
0.375 kV |
2-ch analog in,Resistance measurement, Intrinsically safe
The analog input module allows the direct connection of Pt or Ni resistance sensors and potentiometers located in hazardous environments of Zones 0 and 1.
The WAGO-I/O-SYSTEM 750 must be installed either in Zone 2 or in a non-hazardous area. The 24V supply is derived from the module's power jumper contacts.
The shield (screen) is directly connected to the DIN rail.
LED indicators:
- Green LED (availability ON/OFF)
- Red LED ( short circuit, wire breakage, measuring range overflow/underflow)
Field and system levels are electrically isolated.
<b>Hinweis</b>:
Note: The analog input module must only be operated via Ex i 24VDC power supply!
General information (e.g., installation regulations) on explosion protection is available in the WAGO-I/O-SYSTEM 750 manuals!
<b>Voltage via power jumper contacts</b>: 24 VDC (provided via Ex i supply UO = max. 27.3 V)
<b>ATEX Guideline</b>: EN 60079-0, EN 60079-11, EN 60079-15, EN 60079-26, EN 60079-31
<b>Marking</b>: II 3 (1) GD Ex nA tD [ia] [iaD] I/IIC / IIB A22 IP6X T135°C (T4)
<b>Electric circuit, safety-relevant data</b>: Uo = 7.2 V ; Io = 5.8 mA; Po = 10.5 mW; Characteristic: Linear
<b>Temperature range</b>: -200 °C ... + 850 °C (Pt); -60 °C ... +250 °C (Ni); -80 °C ... +320 °C (Ni 120)